Criterion
-
Construction
-
Flame/smoke integrity
-
Insulation time
-
Typical location
-
Flooring relevance
A-60 and B-15 are SOLAS fire-division classes — ratings for the bulkheads and decks that separate spaces on a ship. The letter defines the construction and how long the division must block flame (A: steel, 60 minutes; B: non-combustible, 30 minutes). The number is how many minutes the unexposed side must stay within the temperature-rise limits.
This short guide decodes the classes, shows where each rating is required on board, and explains what they mean in practice for deck build-ups and flooring — in the language your Class surveyor uses.
SOLAS Chapter II-2 defines three division classes. For outfitting and flooring work, A and B are the two you will meet on every drawing.
Steel or equivalent, stiffened, prevents smoke and flame for a 60-minute standard fire test. Insulated to A-0, A-15, A-30 or A-60 depending on the required temperature-rise time.
Approved non-combustible construction — typically cabin bulkheads, linings and ceilings — holding integrity for a 30-minute test, insulated to B-0 or B-15.
Approved non-combustible materials with no integrity or insulation requirement — no fire test time attached. Used where the tables require only non-combustibility.
Rule of thumb: the letter tells you the construction and integrity time, the number tells you the insulation time — how long the cold side must stay within the temperature-rise limits (139°C average / 180°C at any point for A-class; 139°C average / 225°C at any point for B-class).
Construction
Flame/smoke integrity
Insulation time
Typical location
Flooring relevance
Steel or equivalent
60 min
60 min
Decks/bulkheads at machinery, galleys, cargo
A-60 floating floor build-ups
Steel or equivalent
60 min
30 / 15 min
Intermediate-risk adjacencies per Reg. 9 tables
Thinner insulated deck build-ups
Steel or equivalent
60 min
None (0 min)
Low-risk steel boundaries
Bare or levelled steel deck + approved covering
Approved non-combustible
30 min
15 / 0 min
Cabin bulkheads, corridor linings, ceilings
Rarely the deck — a partition rating
Go deeper on the ratings, the certificates and the certified systems themselves.
The build-up that turns a steel deck into an A-60 division — layer by layer, with the certified GTF Freese systems.
FTP Code parts, wheelmark, Module B+D and the documentation package your surveyor expects.
The complete deck picture zone by zone — from bare steel to finished floor.
IMO/MED certified vinyl, carpet, linoleum and deck systems supplied across the EU.
The questions specifiers ask when the fire plan lands on their desk.
They belong to two different SOLAS division classes. An A-60 division is steel (or equivalent), blocks smoke and flame for a 60-minute standard fire test, and keeps the unexposed side within the temperature-rise limits for the full 60 minutes. A B-15 division is approved non-combustible construction, holds integrity for a 30-minute test, and meets the temperature-rise limit for the first 15 minutes. A-60 is a structural boundary for high-risk adjacencies; B-15 is a lighter partition rating inside accommodation areas.
The number is the insulation time in minutes — how long the cold side of the division must stay within the temperature-rise limits during the fire test. A-class comes as A-0, A-15, A-30, A-60; B-class as B-0 and B-15. The letter fixes construction and integrity time; the number fixes insulation performance.
Wherever the SOLAS II-2 Regulation 9 tables say so for the two space categories either side of the boundary — typically where machinery spaces of category A, galleys or cargo spaces border accommodation, control stations or escape routes. Decks over machinery spaces are the classic case, and the reason A-60 floating floors exist.
Rarely for the deck itself — rated decks are normally A-class, because they are structural steel boundaries. B-15 applies mostly to bulkheads and linings between cabins and corridors. For flooring the practical pairing is: A-class for the deck build-up, FTP Code Part 2/Part 5 approvals for the coverings on top.
No — A-60 is a property of the whole tested division: steel deck plus the complete build-up. A covering on its own carries IMO FTP Code approvals (Part 2 surface flammability, Part 5 primary deck covering). When a datasheet says a product is “used in A-60 constructions”, it means the product is a named component of a type-approved system — the certificate belongs to the system.
Trivaro supplies certified A-60 floating floor systems and IMO/MED approved finishes across the EU — and helps you translate the fire plan into a build-up your classification society signs off first time.
Send the drawing, the required divisions and the deck areas — we respond with a certified system per zone and a B2B quotation.